使用说明书
目 录
1. 引言·····························································2
1.1 简述·······················································2
1.2 技术指标···················································2
1.3 主要功能···················································2
2. 安装····························································3
2.1 安装尺寸···················································3
2.2 接线·······················································4
2.3 开通························································4
3. 操作说明························································5
3.1 面板说明···················································5
3. 2 工作状态说明···············································6
4. 使用调整························································9
5. 报警处理························································9
6. 故障诊断与处理··················································10
7. 维护维修 ·······················································10
8. UC-KT-2021型气体探测器说明书····································11
1.引言
本手册分两部分,分别详细介绍了UC-KB-2008D型气体报警控制器(见图1)及UC-KT-2021型气体探测器的安装,操作及维护。在使用和安装前请仔细阅读本手册。
1.1 简述
UC-KB-2008D型气体报警控制器(以下简称控制器),它与(4~20)mA标准信号气体探测器(以下简称探测器)配合使用。探测器固定安装在可能有气体泄露的室内、外危险场所。控制器接受探测器传来的电信号,并对之进行滤波、模数转换、线性化、浓度计算等一系列处理工作,得到当前所测气体的浓度值。当浓度值达到预先设定的报警值时,控制器即可发出声、光报警及控制信号,提示操作人员采取安全对策或自动启动相关设备,从而避免发生爆炸事故。控制器具有比较完善的自诊断功能,可对系统的各种故障进行处理,以便及时维修。
控制器设计符合国标GB16808-1997《可燃气体报警控制器技术要求和试验方法》,经过公安部消防产品合格评定中心评定,获得产品型式认可证书,编号:ROS。经过北京市相关质量技术监督部门的考核,获得制造计量器具许可证,证号:京[制]01120010号。
1.2 技术指标
供电电压:交流(187~242)V
线性误差限:±5% F.S
功 耗: <50W [与通道容量有关]
工作温度:(0~40)℃
工作湿度:≤95%
通道容量:[本机为12点]
报警设置:高、低限报警两级报警
触点输出:高、低限报警各有1组无源常开触点(电容量220VAC 2A)
传输距离:≤1km(线阻小于20Ω)
箱体规格:[见图1]
重 量:[与通道容量有关]
1.3 主要功能
1.高、低限报警各对应相应的联动输出。
2. 控制器具有自检功能,可对机器的重要部件和面板上所有指示灯进行检查。
3. 带有散热装置。
4.当有下列情形之一时,控制器能在30s内发出与报警信号有明显区别的声、光故障信号:
a. 探测器与控制器连接线断路。
b. 探测器内部元件失效。
c. 控制器主要元件失效。
2 安装
2.1 安装尺寸(如图1)
图1 控制器外观尺寸 图2 控制器接线说明
2.2接线
控制器的后端盖,可见如图2 、图3的接线端子板、电源插座。
A. 插座所带电源线连接到外部电源,将内部电源线插于插座上。并查看插座开关是否开启。
B.直流电源线 [V+、V-]:V+、V-为24V直流电输出端。
C.信号线:信号线采用3芯仪表用控制电缆,与探测器相连,线径及传输距离见表1。将控制器上的P,S,G分别与探测器的P,S,G相连。
表1 线径及传输距离
|
电缆横截面(mm) |
0.75 |
1.0 |
1.5 |
|
远传输距离(M) |
500 |
750 |
1000 |
图3控制器单个接线板示意图
注意: 1、控制器与探测器连接时,注意控制器P,S,G与探测器P,S,G相对应,切勿接反!
2、安装布线工程应符合GB 50093-2002《工业自动化仪表施工
3、验收规范》或《中华人民共和国危险场所电气安装规范》。
D.通讯线:R+、R-,为RS-485信号线。
E.联动输出接线:高限报警的控制输出端子为常开触点HA、HB。低限报警的控制输出接线端子为常开触点LA、LB。输出信号为无源触点信号,联动接线线径应根据所连接设备的具体情况选定。
F. (4~20mA)标准信号输出:I, 标准信号输出端子(相对于直流电源负G)
注意:(4~20mA)标准信号输出功能为可选配功能,定货时必须注明。
2.3 开通
2.3.1 检查安装接线正确无误后,开机。先开主电,再打开备电开关;系统进入预热状态,预热大约1分钟后进入检测状态。
注:控制器在通电后上边的散热风扇自动开启。
3、操作说明
3.1 面板说明
3.1.1 面板示意图(见图4)
图4 操作面板示意图
3.1.2 指示灯说明(见表2)
表2 指示灯说明
|
指示灯说明 |
颜色 |
功能 |
|
报警 |
红 |
发生报警时,该指示灯亮;返回监控态后,按复位键熄灭。 |
|
故障 |
黄 |
探测器存在故障时,该指示灯亮 |
|
电源 |
绿 |
控制器通电时,该指示灯亮 |
3.1.2 功能键说明(见表3)
表3 功能键说明
|
键名 |
功能 |
|
消声|上下 |
当控制器发生报警或故障时,按下此键可以消除声音报警/故障信号。上下键功能见具体功能说明。 |
|
复位|回车 |
按下此键,可使控制器所有报警/故障复位。回车键功能见具体功能说明。 |
|
自检|左右 |
当控制器处于监控状态时,按下此键,即对控制器面板指示灯、显示器、声报警进行功能检查。左右键功能见具体功能说明。 |
3.2 工作状态说明
3.2.1 系统初始化状态
控制器加电,控制器进入系统初始化,此时,浓度显示”----”,时钟显示初始化进行时间。初始化状态大约持续60秒后,系统进入监控状态。
3.2.2 监控状态
在监控状态下, 浓度显示浓度值,无故障,无报警。
3.2.3 自检态
在监控状态下,按自检键,进入自检状态。此时,液晶、面板上所有的指示灯和LED都点亮,蜂鸣器响。
3.2.4 报警态
在监控状态下,如果气体浓度超过报警浓度,控制器即进入报警态。此时报警指示灯亮,“%LEL”显示相应浓度值,同时报警蜂鸣器响。功能号、报警级别显示区显示报警级别。报警后处理措施见<5.报警处理>。
报警级别:A1-低限报警(第1级报警)。
A2-高限报警(第2级报警)。
A3-第3级报警。
A4-第4级报警。
3.2.5 故障态
在监控状态下,若探测器发生故障,控制器即进入故障态。此时故障指示灯亮,故障蜂鸣器响。
故障诊断与处理见<6.故障诊断与处理>。
3.2.6 功能态
在监控状态下,按回车键进入功能态,此时功能号显示区闪烁,此时可以先按上下键再按回车键,切换到子功能号选择、时钟设置、故障记录、报警记录等状态,或者按左右键返回监控状态。
3.2.6.1 子功能号选择
在本功能态下,功能号显示焦点位闪烁,按左右键切换输入焦点,上下键改变焦点位数值,按回车键进入子功能态(见下表4)。
表4 子功能态表
|
功能号 |
功能说明 |
|
1 |
仪表地址 |
|
2 |
通讯速率 |
|
3 |
通道屏蔽 |
|
4 |
探头类型 |
|
5 |
单位 |
|
6 |
小数位数 |
|
7 |
滤波系数 |
|
8 |
报警模式 |
|
9 |
报警有效性 |
|
10 |
量程上限 |
|
11 |
量程下限 |
|
12 |
报警下限(第1报警点) |
|
13 |
报警上限(第2报警点) |
|
14 |
第3报警点 |
|
15 |
第4报警点 |
|
16 |
死区 |
|
17 |
回差 |
|
18 |
显示更改密码 |
|
19 |
密码有效性 |
|
20 |
年份设置 |
|
21 |
月日设置 |
|
22 |
高报脉动有效性设置 |
注:*-本功能无效
3.2.6.1.1 仪表地址
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
注:仪表地址在与上位机通讯时区分通道,有效范围1~254。
3.2.6.1.2 通讯速率
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
注:仪表与上位机通讯采取”9600,n,8,1”模式,采用ModBus RTU协议。通讯波特率默认9600,另有4800, 2400可供选择,分别由0、1、2代表9600、4800、2400三种波特率。
3.2.6.1.3 通讯屏蔽
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
注:1-通道屏蔽有效,通道响应探测器的浓度变化,但不报警;其它-无效
3.2.6.1.4 探头类型
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。见附录1。
3.2.6.1.5 单位
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。见附录2。
3.2.6.1.6 小数位数
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
注:小数位数数值区间为0~3,默认值0。
3.2.6.1.7 滤波系数
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
注:滤波系数数值区间为1~50,默认值20。
3.2.6.1.8报警模式
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
3.2.6.1.9报警有效性
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
3.2.6.1.10 量程上限
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
3.2.6.1.11 量程下限
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
3.2.6.1.12 报警下限(第1报警点)
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
3.2.6.1.13 报警上限(第2报警点)
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
3.2.6.1.14第3报警点
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
3.2.6.1.15第2报警点
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
3.2.6.1.16死区
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
3.2.6.1.17回差
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
4.2.6.1.18 显示更改密码
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
3.2.6.1.19 密码有效性
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态。
注:0-密码无效;1-密码有效,发生报警后,必须输入密码正确,才能复位。
3.2.6.1.20年份设置
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态,
注:本控制器的有效年份为2000~2099。
3.2.6.1.21月日设置
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态
注:浓度显示区前两位为月份,后两位为日期。
3.2.6.1.22高报输出设置
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监控态
注:浓度显示区四位数字全为0,高报后长输出,按复位取消;否则高报脉动输出(闭合时间大约0.5s)。
3.2.6.2 时钟设置
在本功能态下,按左右键进入输入状态和改变输入焦点,上下键更改数值,按回车键确认,返回监测态
3.2.6.3 故障记录
3.3.6.4 报警记录
4.使用调整
在检查安装接线准确无误后,打开电源开关,控制器进入系统初始化状态,大约30秒后,进入监控状态。如果控制器存在故障,按《6故障诊断与处理》进行处理。如果存在通道漂移,按《4.1通道校正》进行调整。报警系统进入正常运行状态。
4.1通道校正
若通道的漂移过大(超过5%F.S),则必须进行通道校正。校正时用电流校正表,在S(+)、G(-)之间输入4mA电流,用一字型螺丝刀调整通道零点调整电位器SW0,使得AB点之间电压差<1mV;,在S(+)、G(-)之间输入16mA电流,当前浓度在75±1%LEL之间摆动即可。
5.报警处理
5.1 在监控状态下,当浓度达到低限报警浓度时,控制器进入报警状态。当浓度达不到低限报警浓度时,按复位键,控制器返回监控状态。、
5.2在报警状态下,按“消声”键,清除报警蜂鸣声,同时消声指示灯亮,再按一次“消声”键,消声状态清除,报警蜂鸣器响,消声指示灯灭。
6.故障诊断与处理
6.1 在故障状态下,故障指示灯亮。此时可以按“消音”键去除故障声音信号。
6.2在故障状态下, 显示“--”说明有故障。可采取以下措施排除故障。
1. 检查控制器与探测器的连线是否正常;
2.若连线无误,用万用表测量S、G间电压在0.2~1V之间.若有异常则表示探测器故障;若无异常,请通知本公司进行处理。
6.3故障处理完后,可以按“复位”键返回监控态。
7. 维护维修
7.1 日常维护
当系统安装完成后,在正常使用过程中,应由专业人员每年对控制器按《4.1通道校正》
进行调整,防止发生漂移。
7.2 若控制器达到使用年限,应及时更换,否则容易造成零漂过大、误报等问题,影响正常生产活动。
7.3 注意环境清洁,如防尘、防水,防油烟等。
地址:北京市通州区永顺西街32号